How do data centre power, build and colocation costs in India compare with other countries?

Last updated

Grid power for large users in India costs about ₹6.2 to ₹10.9 per kWh, a mid-range price (FY2026-27 tariffs). Building is cheap: about US$7.4m per MW, against US$15.2m in the USA (Cushman & Wakefield, 2026). Mumbai colocation costs US$73 to US$105 per kW a month (H1 2025), against US$330 to US$475 in Singapore (Q1 2026).

Key facts

  • In Maharashtra (MSEDCL), large industrial users on high-tension supply pay an average ₹10.88 per kWh (US$0.114). If billed as commercial, they pay ₹16.74 (US$0.176), about 54% more.

    As of FY2026-27. MERC (tariff order, 25 Mar 2026)

  • Singapore's regulated tariff for large users works out at S$0.235 to S$0.246 per kWh all-in (US$0.184 to US$0.192).

    As of Q4 2026. SP Group

  • Building a data centre in India costs about US$7.4m per MW (about ₹70 crore; range US$5.9m to US$9.0m), excluding land and IT equipment. Malaysia is US$9.6m and the USA US$15.2m.

    As of 2026. Cushman & Wakefield cost guides

  • Mumbai colocation rent is ₹7,000 to ₹10,000 per kW a month (US$73 to US$105) for 250 kW to 1 MW, and ₹6,000 to ₹7,500 (US$63 to US$79) for 5 MW or more.

    As of H1 2025. Cushman & Wakefield

  • Colocation asking rents elsewhere: Northern Virginia US$190 to US$235, Frankfurt US$235 to US$265 and Singapore US$330 to US$475 per kW a month.

    As of Q1 2026. CBRE

Rupee to dollar conversions use ₹95.25 per US$ (FBIL reference rate, 13 Oct 2026).

Terms used on this page (10)
Colocation
Renting space, power and cooling in someone else's data centre for your own servers.
Energisation, sanctioned load
Energisation is when the utility actually switches power on. Sanctioned load is the maximum power it has approved for the connection.
DISCOM
A state electricity distribution company. It supplies and bills most large users.
HT, EHV, HV-2
High-tension (usually 11 to 33 kV) and extra-high-voltage supply; higher voltage usually means a lower tariff. HV-2 is Uttar Pradesh's category for large and heavy power users.
Open access, wheeling, cross-subsidy surcharge
Open access lets a large user buy power from a generator other than its DISCOM. Wheeling is the fee for using the DISCOM's wires; the cross-subsidy surcharge compensates the DISCOM for the customer it loses.
Captive, group captive
A power plant at least 26% owned by the users who consume at least 51% of its output. It is exempt from some surcharges.
FY (Indian financial year)
April to March. FY2026-27 runs from 1 Apr 2026 to 31 Mar 2027.
H1, H2
The first half (January to June) and second half (July to December) of a calendar year.
Lakh, crore
1 lakh is 100,000 and 1 crore is 10 million. ₹1 lakh crore is ₹1 trillion, about US$10.5bn at ₹95.25 per US$.
MEP
Mechanical, electrical and plumbing: the building services trades on a data centre build.

Tariffs, build costs and rent, market by market

Grid power in India is mid-priced, not cheap. Building a data centre is cheap. Colocation rent is low by global standards.

Your real bill depends on the state, the supply voltage and the tariff category the state distribution company (DISCOM) gives your site. Energy is about 65% of data centre operating cost (S&P Global, cited by Cushman & Wakefield).

What this means for a GPU cloud

Tariff category is the biggest swing. In Maharashtra a data centre billed as commercial pays about 54% more than one billed as industrial, and several state data centre policies help secure industrial treatment; in Karnataka the current order makes HT commercial slightly cheaper than industrial. Confirm the category per connection, in writing, and compare delivered rupees per kWh.

Grid power for large users: price per kWh

MarketUS$ per kWhAs of
Andhra Pradesh (Visakhapatnam)0.065 to 0.075FY2026-27
Uttar Pradesh (Noida)0.069 to 0.081FY2026-27
Karnataka (Bengaluru)0.079 industry; 0.070 commercialFY2026-27
Telangana (Hyderabad)0.082 to 0.092FY2026-27
Tamil Nadu (Chennai)0.095 to 0.105FY2025-26 rates
Maharashtra (Navi Mumbai, Pune)0.108 to 0.114FY2026-27
Maharashtra, if billed as commercial0.176FY2026-27
USA: Virginia (industrial)0.101Jul 2026
Germany (Frankfurt proxy)0.154H1 2026
Singapore0.184 to 0.192Q4 2026

Indian rows are our all-in estimates from each state's tariff order, for a large user drawing a flat load around the clock. Rupee prices, tariff categories, more countries and every source are under How we got these numbers, below. Foreign rows use different bases, so treat them as a guide, not a like-for-like quote.

How we got these numbers: grid power by market and tariff category

Rupee and local prices, tariff categories and sources for 17 markets
MarketIndicative all-in price per kWhUS$ per kWhBasisAs ofSource
Maharashtra (MSEDCL: Navi Mumbai, Thane-Belapur, Pune)₹10.28 (EHV) to ₹10.88 (HT)0.108 to 0.114Industry at high-tension (HT, 11 to 33 kV) or extra-high voltage (EHV): average billing rate for that sub-category, used to set cross-subsidy. HT industry as a whole averages ₹10.71 in FY27FY2026-27MERC order, 25 Mar 2026
Maharashtra, if billed as commercial₹16.74 (HT)0.176Commercial at high-tension (11 to 33 kV): average billing rate for that sub-category. HT commercial as a whole averages ₹16.78 in FY27FY2026-27MERC order
Tamil Nadu (Chennai)About ₹9.0 (our estimate); ₹9.96 approved average billing rate0.095 to 0.105High-tension industry and IT services (category HT-I), which names data centresFY2025-26 rates; FY2026-27 revision of up to 6% not confirmedTNERC order, 30 Jun 2025
Telangana (Hyderabad)₹7.8 to ₹8.8 (our estimate)0.082 to 0.092High-tension industry (category HT-I(A)), 11 kV to 132 kVFY2026-27TGERC tariff schedule
Uttar Pradesh (Noida, state DISCOMs)₹6.6 to ₹7.7 (our estimate)0.069 to 0.081Large and heavy power users (category HV-2), 11 kV to above 132 kVFY2026-27UPPCL notice of UPERC tariff, Jul 2026
Karnataka (Bengaluru)About ₹7.5 industry; about ₹6.7 commercial (our estimates)0.079; 0.070HT industry; HT commercial is now slightly cheaperFY2026-27KERC order, 27 Mar 2025
Andhra Pradesh (Visakhapatnam)₹6.2 to ₹7.1 (our estimate)0.065 to 0.075High-tension industry, 11 kV to 132 kVFY2026-27APERC order, 25 Mar 2026
SingaporeS$0.235 to S$0.2460.184 to 0.192SP Group regulated tariff for large users at extra-high and high tensionQ4 2026SP Group
Ireland (Dublin proxy)€0.1800.201National non-household average, 70-150 GWh a year, excl. VATH1 2026Eurostat
Germany (Frankfurt proxy)€0.1380.154Same basisH1 2026Eurostat
Netherlands (Amsterdam proxy)€0.1250.140Same basisH1 2026Eurostat
USA: Virginia10.07; 11.68 US cents0.101; 0.117State average, industrial; commercialJul 2026US EIA
USA: Texas7.07; 8.47 US cents0.071; 0.085State average, industrial; commercialJul 2026US EIA
Japan¥28.260.179Business average incl. taxes, not a large-user rateMar 2026GlobalPetrolPrices (low confidence)
MalaysiaRM0.4730.116Business average incl. taxes, not a large-user rateMar 2026GlobalPetrolPrices (low confidence)
UAEAED 0.4050.110Business average incl. taxesMar 2026GlobalPetrolPrices (low confidence)
IndonesiaRp1,114.740.062Business average incl. taxesMar 2026GlobalPetrolPrices (low confidence)

Our Indian all-in estimates assume a flat 24x7 load at 85% load factor and include demand charges and time-of-day effects. They exclude electricity duty, fuel adjustment and open access charges. Exchange rates: ₹95.25, S$1.28, ¥158.1, RM4.09, Rp17,881 per US$ (FBIL and ECB, 13 Oct 2026); AED 3.6725 per US$ (fixed peg); €1 = US$1.119. Foreign rows use different bases, so treat them as a guide, not a like-for-like quote. HT means high-tension supply (usually 11 to 33 kV), EHV extra-high voltage.

Green power and open access: cost building blocks

Renewable purchase prices, open access surcharges, wheeling and the captive exemption
ItemValueUS$As ofSource
Solar bought by MSEDCL₹2.67 to ₹3.04 per kWh0.028 to 0.032FY2026-27 projectionMERC
Firm and dispatchable renewables bought by MSEDCL₹4.46 per kWh0.047FY2026-27 projectionMERC
Cross-subsidy surcharge on third-party open accessMaharashtra ₹2.11; Tamil Nadu ₹1.99; Andhra Pradesh (Vizag DISCOM) ₹1.37 to ₹1.71 per kWh0.014 to 0.022FY2025-26 to FY2026-27MERC; TNERC; APERC
Wheeling charges₹0.81 to ₹1.04 per kWh0.009 to 0.011FY2025-27MERC; TNERC
Inter-state transmission waiver for solar and wind100% if commissioned by 30 Jun 2025, then 75%, 50%, 25%; nil after 30 Jun 2028n/a2026Cushman & Wakefield / Invest India
Green energy open access threshold100 kW; deemed approval after 15 days (as reported; not checked against each state's rules)n/a2026Cushman & Wakefield / Invest India
Captive or group captive (26%+ ownership and 51%+ consumption)Exempt from cross-subsidy and additional surchargesn/aElectricity ActCushman & Wakefield / Invest India

Generation rates are utility purchase benchmarks, not prices a data centre can contract at. The landed cost of round-the-clock green power varies by state and structure; we found no sourced all-in figure.

Construction cost (excluding land and IT equipment)

MarketUS$m per MWRangeSource and date
India (national average)7.4 (about ₹70 crore)5.9 to 9.0Cushman & Wakefield, 2026
Mumbai6.64n/aTurner & Townsend, cited Feb 2026
Indonesia8.36.6 to 11.2Cushman & Wakefield, 2026
Malaysia9.66.9 to 12.0Cushman & Wakefield, 2026
Australia10.07.9 to 12.1Cushman & Wakefield, 2026
Frankfurt11.6n/aTurner & Townsend, Nov 2025
London12.0n/aTurner & Townsend, Nov 2025
Singapore14.5n/aTurner & Townsend, Nov 2025
USA (34 markets)15.211.7 to 18.7Cushman & Wakefield, 2026
Tokyo15.2n/aTurner & Townsend, Nov 2025
Japan (national)16.013.0 to 19.2Cushman & Wakefield, 2026

The two sources use different specifications, so compare within one source. A 100 MW build in India costs about US$220m less than in Malaysia (Cushman & Wakefield). AI-ready builds cost about 7 to 10% more (Turner & Townsend, US data).

Colocation rent (per kW per month)

MarketPriceUS$Deal size and basisAs ofSource
Mumbai₹7,000 to ₹10,000 (250 kW to 1 MW); ₹6,000 to ₹7,500 (5 MW+)73 to 105; 63 to 795-7 kVA racksH1 2025Cushman & Wakefield
Chennai₹7,500 to ₹8,500 (250 kW to 1 MW); ₹6,000 to ₹7,000 (5 MW+)79 to 89; 63 to 73SameH1 2025Cushman & Wakefield
Hyderabad and Delhi NCR₹7,000 to ₹8,500 (250 kW to 1 MW); ₹6,000 to ₹7,000 (5 MW+)73 to 89; 63 to 73SameH1 2025Cushman & Wakefield
Northern VirginiaUS$190 to 235190 to 235250-500 kW; vacancy 0.3%Q1 2026CBRE
FrankfurtUS$235 to 265235 to 265250-500 kW; vacancy 5%Q1 2026CBRE
TokyoAverage US$280280Asking rent; vacancy 6%Q1 2026CBRE
SydneyAverage US$188188Asking rent; vacancy 4.5%Q1 2026CBRE
SingaporeUS$330 to 475 (average US$403)330 to 475Asking rent; vacancy 2%Q1 2026CBRE

Indian figures are the latest city rents Cushman & Wakefield published (H1 2025), so they are about a year older than CBRE's. Whether power is included differs by market. AI-training facilities command about a 60% lease premium (JLL, Jan 2026). Live capacity and vacancy by city are on the operators and live capacity page.

Other cost and schedule factors

Grid connection, equipment lead times, labour, cooling and tax
FactorIndiaElsewhereSource
Grid connectionNo published India-wide lead time. National shortage was 0.03% in FY2025-26, but site substations and sanctioned load decide timingMore than 4 years in primary markets (JLL)JLL; Cushman & Wakefield
Long-lead equipmentImported packages ran 2 to 4 weeks late in H1 2026Global average 33 weeks; generators 40-45 weeks; transformers 20-32 weeksTurner & Townsend; JLL
Construction labour and materialsTender prices forecast to rise 3 to 5%, driven mainly by labour and specialist MEP (mechanical, electrical, plumbing) demand; labour shortages of 30 to 35% across 71 projects in H1 2026; 10 to 15% cost escalation where imported raw materials are involvedn/aTurner & Townsend, 13 Aug 2026
Cooling and efficiencyHot, humid coastal hubs make cooling the biggest non-IT load; liquid cooling narrows the gapCool climates get more free-cooling hoursTurner & Townsend; Uptime Institute
TaxFinance Act 2026: tax exemption to tax year 2046-47 for a foreign company's income from using an Indian company's data centre services (conditions apply). Parliament passed amendments on 10 Aug 2026, but we could not confirm presidential assent or rules (Oct 2026). General information, not tax advicen/aIncome-tax Act 2025, Schedule IV item 13C; Taxation and Other Laws (Amendment) Bill 2026

Want this checked for your own site, power contract or launch plan? See DC advisory.

Sources for this section (17)
  1. MERC. Order in Case No. 75 of 2025 (MSEDCL tariff). 25 Mar 2026
  2. TNERC. Suo-motu Tariff Order No. 6 of 2025. 30 Jun 2025
  3. TGERC. Retail Supply Tariff Schedule FY2026-27. 2026
  4. UPPCL (UPERC-approved). Tariff and rate schedule approved for FY2026-27. 6 Jul 2026
  5. KERC. Tariff charges approved for the control period. 27 Mar 2025
  6. APERC. Tariff for retail sale of electricity, FY2026-27. 25 Mar 2026
  7. SP Group. Historical electricity tariff (Q4 2026). 1 Oct 2026
  8. Eurostat. Electricity prices for non-household consumers (nrg_pc_205). 9 Oct 2026
  9. US EIA. Electric Power Monthly, Table 5.6.A. 24 Sept 2026
  10. GlobalPetrolPrices. Electricity prices around the world. Mar 2026
  11. Turner & Townsend. Data centre construction cost index 2025-2026. 5 Nov 2025
  12. Turner & Townsend. India's construction shifts focus from cost to capacity. 13 Aug 2026
  13. CBRE. Global Data Center Trends 2026. 17 Jun 2026
  14. Cushman & Wakefield. India Data Centre H1 2025 Update (city rents). 2025
  15. JLL. Global data center sector to nearly double to 200GW. 6 Jan 2026
  16. ECB. Euro foreign exchange reference rates (USD, IDR, JPY, MYR, SGD). 13 Oct 2026
  17. RBI. FBIL reference rate, INR per US$ 95.2477. 13 Oct 2026

Power, build and rent costs

Frequently asked questions

  • On FY2026-27 industrial tariffs, indicative all-in prices run from about ₹6.2 per kWh (US$0.065) in Andhra Pradesh to ₹10.9 (US$0.114), Maharashtra's average billing rate for high-tension industry. Uttar Pradesh is about ₹6.6 to ₹7.7, Karnataka about ₹7.5 and Telangana about ₹7.8 to ₹8.8, while Tamil Nadu is about ₹9.0 on FY2025-26 rates. Our state estimates assume a flat 24x7 load at 85% load factor and exclude electricity duty, fuel adjustment and open access charges.

  • It is cheaper than Singapore and Europe, and in the same range as US states. Singapore's regulated rate is US$0.184 to US$0.192 per kWh (SP Group, Q4 2026), and users taking 70 to 150 GWh a year pay an average US$0.201 in Ireland, US$0.154 in Germany and US$0.140 in the Netherlands (Eurostat, H1 2026). US industry pays an average US$0.101 in Virginia and US$0.071 in Texas (US EIA, Jul 2026). Foreign figures use different bases, so treat them as a guide, not a like-for-like quote.

  • Each state distribution company (DISCOM) decides whether your connection is billed as industrial or commercial, and the gap can be large. In Maharashtra, high-tension (HT) commercial supply averages ₹16.74 per kWh against ₹10.88 for HT industry in FY2026-27, about 54% more (MERC). In Karnataka the current order makes HT commercial slightly cheaper than industry, and several state data centre policies, such as Tamil Nadu's 2021 policy, help secure industrial treatment. This is general information, not legal advice: get the category confirmed in writing for each connection.

  • About US$7.4m per MW (about ₹70 crore), within a range of US$5.9m to US$9.0m, excluding land and IT equipment (Cushman & Wakefield, 2026). On the same basis Malaysia costs US$9.6m, the USA US$15.2m and Japan US$16.0m, so a 100 MW build in India costs about US$220m less than in Malaysia. Turner & Townsend puts Mumbai at US$6.64m (cited Feb 2026) against US$14.5m in Singapore (Nov 2025); compare within one source, as specifications differ. Indian tender prices are forecast to rise 3 to 5%, driven mainly by labour and specialist mechanical, electrical and plumbing (MEP) work (Turner & Townsend, 13 Aug 2026).

  • Mumbai rents were ₹7,000 to ₹10,000 per kW a month (US$73 to US$105) for 250 kW to 1 MW and ₹6,000 to ₹7,500 (US$63 to US$79) for 5 MW or more, while Chennai, Hyderabad and Delhi NCR ranged from ₹6,000 to ₹8,500 (Cushman & Wakefield, H1 2025). CBRE's Q1 2026 asking rents were US$190 to US$235 in Northern Virginia, US$235 to US$265 in Frankfurt and US$330 to US$475 in Singapore. The Indian figures are about a year older, and whether power is included differs by market. Space for AI training commands about a 60% lease premium (JLL, Jan 2026).

  • Generally yes. Cushman & Wakefield and Invest India (2026) report green energy open access from 100 kW, with deemed approval after 15 days; we have not checked this against each state's rules. Buying from a third party adds a cross-subsidy surcharge of ₹2.11 per kWh in Maharashtra, ₹1.99 in Tamil Nadu and ₹1.37 to ₹1.71 in Andhra Pradesh (Vizag DISCOM), plus wheeling of ₹0.81 to ₹1.04 (FY2025-26 to FY2026-27), though captive or group captive set-ups (26%+ ownership and 51%+ consumption) are exempt from cross-subsidy and additional surcharges. This is general information, not legal advice, and we found no sourced all-in cost for round-the-clock green power.

FlexiCloud DC advisory

Planning capacity in India?

FlexiCloud DC advisory can check the tariff category, green power options and power pass-through terms in your own colocation or power offer before you sign.

More from the India data centre guide

  • Operators and live capacity

    Live MW and vacancy for seven cities, led by Mumbai with 890 MW (H1 2026), plus live capacity, pipeline and owners for 14 major operators, each figure with its date and source.

  • Why India: outlook and risks

    India produces nearly 20% of the world's data but hosts about 3% of its data centres (Jun 2025). See the capacity forecasts to 2030, the demand behind them, and the risks: grid delays, water, unsettled rules, vacancy and unbuilt announcements.

  • Neocloud entry guide

    Entry models from colocation to build-to-suit, the Indian and US rules that apply (CERT-In, DPDP, export controls), IndiaAI reference GPU prices, verified state incentives and a 14-point checklist. Also why the 2047 tax exemption probably does not fit a neocloud that owns its GPUs.

Capacity is being built. Choosing where to run still matters.

More supply means more choice of site, region and provider, not less need for someone to help you pick. Whether you are planning your own capacity in India or need GPUs now, we deal with the operators and providers so you do not have to.

GPU capacity

Need B300 or B200 capacity?

Tell us your GPU count, term and region. We source the best-fit nodes across our provider network in India, the EU and the US, and confirm availability and lead time for your region before you order.